You can not select more than 25 topics
Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
184 lines
7.4 KiB
184 lines
7.4 KiB
3 years ago
|
<?xml version="1.0" encoding="UTF-8"?>
|
||
|
<zabbix_export>
|
||
|
<version>5.0</version>
|
||
|
<date>2021-06-19T12:20:39Z</date>
|
||
|
<groups>
|
||
|
<group>
|
||
|
<name>Modèles</name>
|
||
|
</group>
|
||
|
<group>
|
||
|
<name>Templates</name>
|
||
|
</group>
|
||
|
</groups>
|
||
|
<templates>
|
||
|
<template>
|
||
|
<template>Template_UPS_APC_SNMP</template>
|
||
|
<name>Template_UPS_APC_SNMP</name>
|
||
|
<groups>
|
||
|
<group>
|
||
|
<name>Modèles</name>
|
||
|
</group>
|
||
|
<group>
|
||
|
<name>Templates</name>
|
||
|
</group>
|
||
|
</groups>
|
||
|
<items>
|
||
|
<item>
|
||
|
<name>Température de la batterie</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.2.2.2.0</snmp_oid>
|
||
|
<key>upsAdvBatteryTemperature</key>
|
||
|
<delay>5m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<request_method>POST</request_method>
|
||
|
<triggers>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}>40</expression>
|
||
|
<name>Température élevée</name>
|
||
|
<priority>HIGH</priority>
|
||
|
</trigger>
|
||
|
</triggers>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>Charge actuelle (ampères)</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.4.2.4.0</snmp_oid>
|
||
|
<key>upsAdvOutputCurrent</key>
|
||
|
<delay>5m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<value_type>FLOAT</value_type>
|
||
|
<units>a</units>
|
||
|
<request_method>POST</request_method>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>Charge (%)</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.4.2.3.0</snmp_oid>
|
||
|
<key>upsAdvOutputLoad</key>
|
||
|
<delay>5m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<value_type>FLOAT</value_type>
|
||
|
<request_method>POST</request_method>
|
||
|
<triggers>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}>95</expression>
|
||
|
<name>APC: Output Load Too High - {HOSTNAME}</name>
|
||
|
<status>DISABLED</status>
|
||
|
<priority>DISASTER</priority>
|
||
|
</trigger>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}>90</expression>
|
||
|
<name>Onduleur en surcharge</name>
|
||
|
<priority>HIGH</priority>
|
||
|
</trigger>
|
||
|
</triggers>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>Témoin de remplacement de la batterie</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.2.2.4.0</snmp_oid>
|
||
|
<key>upsAdvReplaceBatteryIndicator</key>
|
||
|
<delay>10m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<valuemap>
|
||
|
<name>APC Battery Replacement Status</name>
|
||
|
</valuemap>
|
||
|
<request_method>POST</request_method>
|
||
|
<triggers>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}<>1</expression>
|
||
|
<name>Batterie défectueuse</name>
|
||
|
<priority>DISASTER</priority>
|
||
|
</trigger>
|
||
|
</triggers>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>Temps restant</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.2.2.3.0</snmp_oid>
|
||
|
<key>upsAdvRunTimeRemaining</key>
|
||
|
<delay>3m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<units>s</units>
|
||
|
<preprocessing>
|
||
|
<step>
|
||
|
<type>MULTIPLIER</type>
|
||
|
<params>0.01</params>
|
||
|
</step>
|
||
|
</preprocessing>
|
||
|
<request_method>POST</request_method>
|
||
|
<triggers>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}<5</expression>
|
||
|
<name>APC: Run Time Remaining Critical Level - {HOSTNAME}</name>
|
||
|
<status>DISABLED</status>
|
||
|
<priority>DISASTER</priority>
|
||
|
</trigger>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}<10</expression>
|
||
|
<name>Niveau d'énergie faible</name>
|
||
|
<priority>HIGH</priority>
|
||
|
</trigger>
|
||
|
</triggers>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>État de la batterie</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.2.1.1.0</snmp_oid>
|
||
|
<key>upsBasicBatteryStatus</key>
|
||
|
<delay>3m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<valuemap>
|
||
|
<name>APC Battery Status</name>
|
||
|
</valuemap>
|
||
|
<request_method>POST</request_method>
|
||
|
<triggers>
|
||
|
<trigger>
|
||
|
<expression>{last(0)}<>2</expression>
|
||
|
<name>Perte de l'alimentation</name>
|
||
|
<priority>DISASTER</priority>
|
||
|
</trigger>
|
||
|
</triggers>
|
||
|
</item>
|
||
|
<item>
|
||
|
<name>Durée sur batterie</name>
|
||
|
<type>SNMP_AGENT</type>
|
||
|
<snmp_oid>.1.3.6.1.4.1.318.1.1.1.2.1.2.0</snmp_oid>
|
||
|
<key>upsBasicBatteryTimeOnBattery</key>
|
||
|
<delay>3m</delay>
|
||
|
<history>30d</history>
|
||
|
<trends>1095d</trends>
|
||
|
<units>s</units>
|
||
|
<preprocessing>
|
||
|
<step>
|
||
|
<type>MULTIPLIER</type>
|
||
|
<params>0.01</params>
|
||
|
</step>
|
||
|
</preprocessing>
|
||
|
<request_method>POST</request_method>
|
||
|
</item>
|
||
|
</items>
|
||
|
<macros>
|
||
|
<macro>
|
||
|
<macro>{$COMMUNITY}</macro>
|
||
|
<value>public</value>
|
||
|
</macro>
|
||
|
</macros>
|
||
|
</template>
|
||
|
</templates>
|
||
|
<value_maps>
|
||
|
<value_map>
|
||
|
<name>APC Battery Replacement Status</name>
|
||
|
</value_map>
|
||
|
<value_map>
|
||
|
<name>APC Battery Status</name>
|
||
|
</value_map>
|
||
|
</value_maps>
|
||
|
</zabbix_export>
|