5.0
2021-06-19T10:43:09Z
Templates
Template_UPS_CyberPower_SNMP
Template_UPS_CyberPower_SNMP
Template_SNMP_Device
Templates
Battery
Information
Input
Output
RMCARD
-
Capacity
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.2.1.0
battery.capacity
120s
30d
%
CPS-MIB::upsAdvanceBatteryCapacity - the battery capacity expressed in percentage
Battery
{last()}<10
Battery charge is less than 10%
HIGH
{last()}<20
Battery charge is less than 20%
WARNING
Battery charge is less than 10%
{Template_UPS_CyberPower_SNMP:battery.capacity.last()}<10
-
Remaining Runtime
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.2.4.0
battery.RemainingRuntime
120s
30d
FLOAT
min
CPS-MIB::upsAdvanceBatteryRunTimeRemaining - the UPS battery remaining run time
Battery
MULTIPLIER
0.00016666666666
-
Replace Indicator
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.2.5.0
battery.ReplaceIndicator
1h
30d
0
CPS-MIB::upsAdvanceBatteryReplaceIndicator - this value indicates if UPS batteries need to be replaced
Battery
CyberPower UPS Battery Replacement Indicator
{last()}<>1
Battery should be replaced
AVERAGE
-
Battery status
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.1.1.0
battery.Status
120s
30d
CPS-MIB::upsBaseBatteryStatus - the UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be configured by the upsAdvanceConfigLowBatteryRunTime.
Battery
CyberPower UPS Battery Status
-
Time on Battery
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.1.2.0
battery.TimeOnBattery
120s
30d
FLOAT
min
CPS-MIB::upsBaseBatteryTimeOnBattery - the UPS wasted battery time since the UPS has transfered to backup mode
Battery
MULTIPLIER
0.00016666666666
-
Voltage Rating
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.2.8.0
battery.VoltageRating
1h
30d
0
V
CPS-MIB::upsAdvanceBatteryVoltageRating - the DC voltage rating of the battery set
Battery
-
Last Fail Cause
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.3.2.5.0
input.FailCause
1h
1w
0
CPS-MIB::upsAdvanceInputLineFailCause - The reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reason of input voltage over the high transfer vloltage. - brownout(3), if UPS switch to battery mode by reason of input voltage under the low transfer vloltage. - selfTest(4), if the UPS was commanded to do a self test.
Input
CyberPower UPS Input Fail Cause
-
Input frequency
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.3.2.4.0
input.Frequency
120s
30d
Hz
CPS-MIB::upsAdvanceInputFrequency - the input line frequency in 1/10 Hz
Input
MULTIPLIER
0.1
-
Input status
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.3.2.6.0
input.Status
60s
30d
CPS-MIB::upsAdvanceInputStatus - display the present status of the utility power supplied to the UPS
Input
CyberPower UPS Input Status
{last()}<>1
Issue on power input
WARNING
-
Input voltage
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.3.2.1.0
input.Voltage
120s
30d
V
CPS-MIB::upsAdvanceInputLineVoltage - the input line voltage in 1/10 VAC
Input
MULTIPLIER
0.1
-
Output frequency
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.4.2.2.0
output.Frequency
120s
30d
Hz
CPS-MIB::upsAdvanceOutputFrequency - the UPS output frequency in 1/10 Hz
Output
MULTIPLIER
0.1
-
Load (%)
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.4.2.3.0
output.Load
120s
30d
%
CPS-MIB::upsAdvanceOutputLoad - the UPS output load expressed in percentage
Output
{last()}>80
High output power load
WARNING
-
Load (watts)
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.4.2.5.0
output.LoadW
120s
30d
!W
CPS-MIB::upsAdvanceOutputPower - the total output active power of the UPS system in W
Output
-
Output status
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.4.1.1.0
output.Status
120s
30d
CPS-MIB::upsBaseOutputStatus - the UPS output status
Output
CyberPower UPS Output Status
{last()}=3
UPS is on battery
AVERAGE
-
Output voltage
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.4.2.1.0
output.Voltage
120s
30d
V
CPS-MIB::upsAdvanceOutputVoltage - the UPS output voltage in 1/10 VAC
Output
MULTIPLIER
0.1
-
Firmware Revision
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.2.4.0
rmcard.FirmwareRevision
1h
1w
0
TEXT
CPS-MIB::upsAdvanceIdentAgentFirmwareRevision - the SNMP agent firmware revision
RMCARD
-
Firmware Version
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.2.1.0
ups.info.FirmwareVersion
1h
1w
0
TEXT
CPS-MIB::upsAdvanceIdentFirmwareRevision - the UPS firmware revision
Information
-
Load Power
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.2.7.0
ups.info.LoadPower
1h
1w
0
!W
CPS-MIB::upsAdvanceIdentLoadPower - the power rating(Watts) of the UPS
Information
-
Model
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.1.1.0
ups.info.Model
1h
1w
0
TEXT
CPS-MIB::upsBaseIdentModel - the UPS model name
MODEL
Information
-
Name
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.1.2.0
ups.info.Name
1h
1w
0
TEXT
CPS-MIB::upsBaseIdentName - the UPS identified name could be set by the administrator
NAME
Information
-
Power Rating
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.1.2.6.0
ups.info.PowerRating
1h
1w
0
!VA
CPS-MIB::upsAdvanceIdentPowerRating - the Volt-Amp rating of the UPS
Information
-
Temperature
SNMP_AGENT
1.3.6.1.4.1.3808.1.1.1.2.2.3.0
ups.temperature
120s
30d
°C
Information
MULTIPLIER
0.1
{last()}>42
RECOVERY_EXPRESSION
{last()}<40
UPS temperature is {ITEM.LASTVALUE1}
WARNING
{$SNMP_COMMUNITY}
public
CyberPower UPS Battery Replacement Indicator
1
noBatteryNeedsReplacing
2
batteryNeedsReplacing
CyberPower UPS Battery Status
1
unknown
2
batteryNormal
3
batteryLow
CyberPower UPS Input Fail Cause
1
noTransfer
2
highLineVoltage
3
brownout
4
selfTest
CyberPower UPS Input Status
1
normal
2
overVoltage
3
underVoltage
4
frequencyFailure
5
blackout
CyberPower UPS Output Status
1
unknown
2
onLine
3
onBattery
4
onBoost
5
onSleep
6
off
7
rebooting