<?xml version="1.0" encoding="UTF-8"?>
|
|
<zabbix_export>
|
|
<version>5.0</version>
|
|
<date>2021-06-19T10:43:09Z</date>
|
|
<groups>
|
|
<group>
|
|
<name>Templates</name>
|
|
</group>
|
|
</groups>
|
|
<templates>
|
|
<template>
|
|
<template>Template_UPS_CyberPower_SNMP</template>
|
|
<name>Template_UPS_CyberPower_SNMP</name>
|
|
<templates>
|
|
<template>
|
|
<name>Template_SNMP_Device</name>
|
|
</template>
|
|
</templates>
|
|
<groups>
|
|
<group>
|
|
<name>Templates</name>
|
|
</group>
|
|
</groups>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
<application>
|
|
<name>Input</name>
|
|
</application>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
<application>
|
|
<name>RMCARD</name>
|
|
</application>
|
|
</applications>
|
|
<items>
|
|
<item>
|
|
<name>Capacity</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.2.1.0</snmp_oid>
|
|
<key>battery.capacity</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>%</units>
|
|
<description>CPS-MIB::upsAdvanceBatteryCapacity - the battery capacity expressed in percentage</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}<10</expression>
|
|
<name>Battery charge is less than 10%</name>
|
|
<priority>HIGH</priority>
|
|
</trigger>
|
|
<trigger>
|
|
<expression>{last()}<20</expression>
|
|
<name>Battery charge is less than 20%</name>
|
|
<priority>WARNING</priority>
|
|
<dependencies>
|
|
<dependency>
|
|
<name>Battery charge is less than 10%</name>
|
|
<expression>{Template_UPS_CyberPower_SNMP:battery.capacity.last()}<10</expression>
|
|
</dependency>
|
|
</dependencies>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
<item>
|
|
<name>Remaining Runtime</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.2.4.0</snmp_oid>
|
|
<key>battery.RemainingRuntime</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<value_type>FLOAT</value_type>
|
|
<units>min</units>
|
|
<description>CPS-MIB::upsAdvanceBatteryRunTimeRemaining - the UPS battery remaining run time</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.00016666666666</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Replace Indicator</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.2.5.0</snmp_oid>
|
|
<key>battery.ReplaceIndicator</key>
|
|
<delay>1h</delay>
|
|
<history>30d</history>
|
|
<trends>0</trends>
|
|
<description>CPS-MIB::upsAdvanceBatteryReplaceIndicator - this value indicates if UPS batteries need to be replaced</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
<valuemap>
|
|
<name>CyberPower UPS Battery Replacement Indicator</name>
|
|
</valuemap>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}<>1</expression>
|
|
<name>Battery should be replaced</name>
|
|
<priority>AVERAGE</priority>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
<item>
|
|
<name>Battery status</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.1.1.0</snmp_oid>
|
|
<key>battery.Status</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<description>CPS-MIB::upsBaseBatteryStatus - the UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be configured by the upsAdvanceConfigLowBatteryRunTime.</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
<valuemap>
|
|
<name>CyberPower UPS Battery Status</name>
|
|
</valuemap>
|
|
</item>
|
|
<item>
|
|
<name>Time on Battery</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.1.2.0</snmp_oid>
|
|
<key>battery.TimeOnBattery</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<value_type>FLOAT</value_type>
|
|
<units>min</units>
|
|
<description>CPS-MIB::upsBaseBatteryTimeOnBattery - the UPS wasted battery time since the UPS has transfered to backup mode</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.00016666666666</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Voltage Rating</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.2.8.0</snmp_oid>
|
|
<key>battery.VoltageRating</key>
|
|
<delay>1h</delay>
|
|
<history>30d</history>
|
|
<trends>0</trends>
|
|
<units>V</units>
|
|
<description>CPS-MIB::upsAdvanceBatteryVoltageRating - the DC voltage rating of the battery set</description>
|
|
<applications>
|
|
<application>
|
|
<name>Battery</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Last Fail Cause</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.3.2.5.0</snmp_oid>
|
|
<key>input.FailCause</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<description>CPS-MIB::upsAdvanceInputLineFailCause - The reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reason of input voltage over the high transfer vloltage. - brownout(3), if UPS switch to battery mode by reason of input voltage under the low transfer vloltage. - selfTest(4), if the UPS was commanded to do a self test.</description>
|
|
<applications>
|
|
<application>
|
|
<name>Input</name>
|
|
</application>
|
|
</applications>
|
|
<valuemap>
|
|
<name>CyberPower UPS Input Fail Cause</name>
|
|
</valuemap>
|
|
</item>
|
|
<item>
|
|
<name>Input frequency</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.3.2.4.0</snmp_oid>
|
|
<key>input.Frequency</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>Hz</units>
|
|
<description>CPS-MIB::upsAdvanceInputFrequency - the input line frequency in 1/10 Hz</description>
|
|
<applications>
|
|
<application>
|
|
<name>Input</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.1</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Input status</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.3.2.6.0</snmp_oid>
|
|
<key>input.Status</key>
|
|
<delay>60s</delay>
|
|
<history>30d</history>
|
|
<description>CPS-MIB::upsAdvanceInputStatus - display the present status of the utility power supplied to the UPS</description>
|
|
<applications>
|
|
<application>
|
|
<name>Input</name>
|
|
</application>
|
|
</applications>
|
|
<valuemap>
|
|
<name>CyberPower UPS Input Status</name>
|
|
</valuemap>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}<>1</expression>
|
|
<name>Issue on power input</name>
|
|
<priority>WARNING</priority>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
<item>
|
|
<name>Input voltage</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.3.2.1.0</snmp_oid>
|
|
<key>input.Voltage</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>V</units>
|
|
<description>CPS-MIB::upsAdvanceInputLineVoltage - the input line voltage in 1/10 VAC</description>
|
|
<applications>
|
|
<application>
|
|
<name>Input</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.1</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Output frequency</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.4.2.2.0</snmp_oid>
|
|
<key>output.Frequency</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>Hz</units>
|
|
<description>CPS-MIB::upsAdvanceOutputFrequency - the UPS output frequency in 1/10 Hz</description>
|
|
<applications>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.1</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Load (%)</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.4.2.3.0</snmp_oid>
|
|
<key>output.Load</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>%</units>
|
|
<description>CPS-MIB::upsAdvanceOutputLoad - the UPS output load expressed in percentage</description>
|
|
<applications>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
</applications>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}>80</expression>
|
|
<name>High output power load</name>
|
|
<priority>WARNING</priority>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
<item>
|
|
<name>Load (watts)</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.4.2.5.0</snmp_oid>
|
|
<key>output.LoadW</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>!W</units>
|
|
<description>CPS-MIB::upsAdvanceOutputPower - the total output active power of the UPS system in W</description>
|
|
<applications>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Output status</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.4.1.1.0</snmp_oid>
|
|
<key>output.Status</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<description>CPS-MIB::upsBaseOutputStatus - the UPS output status</description>
|
|
<applications>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
</applications>
|
|
<valuemap>
|
|
<name>CyberPower UPS Output Status</name>
|
|
</valuemap>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}=3</expression>
|
|
<name>UPS is on battery</name>
|
|
<priority>AVERAGE</priority>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
<item>
|
|
<name>Output voltage</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.4.2.1.0</snmp_oid>
|
|
<key>output.Voltage</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>V</units>
|
|
<description>CPS-MIB::upsAdvanceOutputVoltage - the UPS output voltage in 1/10 VAC</description>
|
|
<applications>
|
|
<application>
|
|
<name>Output</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.1</params>
|
|
</step>
|
|
</preprocessing>
|
|
</item>
|
|
<item>
|
|
<name>Firmware Revision</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.2.4.0</snmp_oid>
|
|
<key>rmcard.FirmwareRevision</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<value_type>TEXT</value_type>
|
|
<description>CPS-MIB::upsAdvanceIdentAgentFirmwareRevision - the SNMP agent firmware revision</description>
|
|
<applications>
|
|
<application>
|
|
<name>RMCARD</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Firmware Version</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.2.1.0</snmp_oid>
|
|
<key>ups.info.FirmwareVersion</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<value_type>TEXT</value_type>
|
|
<description>CPS-MIB::upsAdvanceIdentFirmwareRevision - the UPS firmware revision</description>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Load Power</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.2.7.0</snmp_oid>
|
|
<key>ups.info.LoadPower</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<units>!W</units>
|
|
<description>CPS-MIB::upsAdvanceIdentLoadPower - the power rating(Watts) of the UPS</description>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Model</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.1.1.0</snmp_oid>
|
|
<key>ups.info.Model</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<value_type>TEXT</value_type>
|
|
<description>CPS-MIB::upsBaseIdentModel - the UPS model name</description>
|
|
<inventory_link>MODEL</inventory_link>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Name</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.1.2.0</snmp_oid>
|
|
<key>ups.info.Name</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<value_type>TEXT</value_type>
|
|
<description>CPS-MIB::upsBaseIdentName - the UPS identified name could be set by the administrator</description>
|
|
<inventory_link>NAME</inventory_link>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Power Rating</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.1.2.6.0</snmp_oid>
|
|
<key>ups.info.PowerRating</key>
|
|
<delay>1h</delay>
|
|
<history>1w</history>
|
|
<trends>0</trends>
|
|
<units>!VA</units>
|
|
<description>CPS-MIB::upsAdvanceIdentPowerRating - the Volt-Amp rating of the UPS</description>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
</item>
|
|
<item>
|
|
<name>Temperature</name>
|
|
<type>SNMP_AGENT</type>
|
|
<snmp_oid>1.3.6.1.4.1.3808.1.1.1.2.2.3.0</snmp_oid>
|
|
<key>ups.temperature</key>
|
|
<delay>120s</delay>
|
|
<history>30d</history>
|
|
<units>°C</units>
|
|
<applications>
|
|
<application>
|
|
<name>Information</name>
|
|
</application>
|
|
</applications>
|
|
<preprocessing>
|
|
<step>
|
|
<type>MULTIPLIER</type>
|
|
<params>0.1</params>
|
|
</step>
|
|
</preprocessing>
|
|
<triggers>
|
|
<trigger>
|
|
<expression>{last()}>42</expression>
|
|
<recovery_mode>RECOVERY_EXPRESSION</recovery_mode>
|
|
<recovery_expression>{last()}<40</recovery_expression>
|
|
<name>UPS temperature is {ITEM.LASTVALUE1}</name>
|
|
<priority>WARNING</priority>
|
|
</trigger>
|
|
</triggers>
|
|
</item>
|
|
</items>
|
|
<macros>
|
|
<macro>
|
|
<macro>{$SNMP_COMMUNITY}</macro>
|
|
<value>public</value>
|
|
</macro>
|
|
</macros>
|
|
</template>
|
|
</templates>
|
|
<value_maps>
|
|
<value_map>
|
|
<name>CyberPower UPS Battery Replacement Indicator</name>
|
|
<mappings>
|
|
<mapping>
|
|
<value>1</value>
|
|
<newvalue>noBatteryNeedsReplacing</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>2</value>
|
|
<newvalue>batteryNeedsReplacing</newvalue>
|
|
</mapping>
|
|
</mappings>
|
|
</value_map>
|
|
<value_map>
|
|
<name>CyberPower UPS Battery Status</name>
|
|
<mappings>
|
|
<mapping>
|
|
<value>1</value>
|
|
<newvalue>unknown</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>2</value>
|
|
<newvalue>batteryNormal</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>3</value>
|
|
<newvalue>batteryLow</newvalue>
|
|
</mapping>
|
|
</mappings>
|
|
</value_map>
|
|
<value_map>
|
|
<name>CyberPower UPS Input Fail Cause</name>
|
|
<mappings>
|
|
<mapping>
|
|
<value>1</value>
|
|
<newvalue>noTransfer</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>2</value>
|
|
<newvalue>highLineVoltage</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>3</value>
|
|
<newvalue>brownout</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>4</value>
|
|
<newvalue>selfTest</newvalue>
|
|
</mapping>
|
|
</mappings>
|
|
</value_map>
|
|
<value_map>
|
|
<name>CyberPower UPS Input Status</name>
|
|
<mappings>
|
|
<mapping>
|
|
<value>1</value>
|
|
<newvalue>normal</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>2</value>
|
|
<newvalue>overVoltage</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>3</value>
|
|
<newvalue>underVoltage</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>4</value>
|
|
<newvalue>frequencyFailure</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>5</value>
|
|
<newvalue>blackout</newvalue>
|
|
</mapping>
|
|
</mappings>
|
|
</value_map>
|
|
<value_map>
|
|
<name>CyberPower UPS Output Status</name>
|
|
<mappings>
|
|
<mapping>
|
|
<value>1</value>
|
|
<newvalue>unknown</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>2</value>
|
|
<newvalue>onLine</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>3</value>
|
|
<newvalue>onBattery</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>4</value>
|
|
<newvalue>onBoost</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>5</value>
|
|
<newvalue>onSleep</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>6</value>
|
|
<newvalue>off</newvalue>
|
|
</mapping>
|
|
<mapping>
|
|
<value>7</value>
|
|
<newvalue>rebooting</newvalue>
|
|
</mapping>
|
|
</mappings>
|
|
</value_map>
|
|
</value_maps>
|
|
</zabbix_export>
|
|
|